All tools
Math & Everyday

Voltage Drop Calculator

Voltage drop across a wire run from gauge, current, and distance, against NEC's 3%/5% guidance.

🔒 Runs entirely in your browser — nothing here is ever uploaded

About the Voltage Drop Calculator

Calculates the voltage drop across a wire run from the wire's gauge (AWG), current, and one-way distance, using real NEC Chapter 9 Table 8 copper-conductor resistance values — flagged against the NEC's commonly cited 3%/5% voltage-drop recommendations.

100% Free Runs in Your Browser No Sign-Up Required
How to use it
  1. Select the wire gauge (AWG) and circuit type (DC/single-phase, or three-phase).
  2. Enter the current and one-way distance.
  3. Enter the source voltage.
  4. Read the voltage drop, percentage drop, and voltage reaching the load.
Formula
Voltage drop = multiplier × current × resistance-per-1000ft × one-way distance ÷ 1000. Multiplier = 2 for DC/single-phase or √3 for three-phase. Percent drop = voltage drop ÷ source voltage × 100.
Worked example

12 AWG copper wire carrying 15A over a 50ft one-way DC/single-phase run at 120V: a voltage drop of about 2.97V (2.48%).

NEC Chapter 9 Table 8 — copper resistance (ohms per 1000 ft, 75°C)
NEC Chapter 9 Table 8 — copper resistance (ohms per 1000 ft, 75°C)
AWGΩ / 1000 ft
60.491
80.778
101.24
121.98
143.14
Interpreting your result

Uses NEC Chapter 9, Table 8 resistance values for uncoated copper at 75°C. The 3%/5% thresholds (NEC 210.19(A) Informational Note) are recommendations, not a mandatory NEC requirement in most jurisdictions. Consult a licensed electrician for any real installation.

Recommendations
  • Three-phase circuits have lower voltage drop than single-phase for the same current/distance/gauge.
  • Doubling the distance or current doubles the voltage drop — both scale linearly.
  • The 3%/5% thresholds are recommendations for efficiency, not safety limits.
Frequently asked questions
Current travels from source to load and back to complete the circuit.
Sources